1427 SE 12th Terrace, Cape Coral · Wednesday, Oct 8, 2026 · with Joseph

Your system is running well. One part needs replacing today to protect the compressor.

Carrier heat pump3 tonInstalled 2019R-410A
13
readings checked
10
good
2
watch
1
needs attention

Pat, here's everything we checked today, in one place. Share it with anyone who helps you decide.

Done today
  • Full cooling tune-up
  • New 20×25×1 filter (yours was 4 months in)
  • Drain line flushed and tested
  • Outdoor coil rinsed
  • Contactor, wiring and connections checked
  • 15-minute air test in the living room

Your system

Measured live with Fieldpiece Job Link probes and a meter at the unit. Targets come from the data plate on your equipment, not a generic rule.

good watch we act here today last visit, April

Your air

15-minute test in the living room, 2:10–2:25 pm. Two people home, no cooking or cleaning in the last hour, doors closed, fan on Auto, set to 76°.

good watch we act here today last visit

Standards for air are written for 24-hour and yearly averages, and this is a consumer-grade sensor, so treat these as a check, not a measure of exposure. Scale: EPA and ASHRAE guidance.

SEE THE FULL AIR QUALITY REPORT ›

What we found

The one item that needs attention is first, then the two watch items. Everything else we checked is listed as fine at the bottom.

Run capacitor is below its toleranceNeeds attention
45 µF ±6%41.6
Meter on your run capacitor
Reading
41.6 µF on a part rated 45 µF, 7.6% low. The label allows 6%. It was 43.0 in April, so it is drifting down.
Means
This part gives the compressor and fan their kick-start and keeps them running smoothly. When it's weak, the compressor starts rough and draws more current, which makes it run hotter. Both motors still read normal today, so we caught it early.
If left alone
Rough starts and extra heat wear the compressor, the most expensive part in your system. When the capacitor finally fails, cooling stops until it's replaced.
Air was pushing harder than it shouldWatch
Your old filter, 4 months in
Reading
Static pressure 0.72 before, 0.58 after the new filter. The plate max is 0.50.
Means
The filter was the biggest cause and it's fixed. The system still pushes a little harder than the maker designed for, which most often points to a small return.
If left alone
Higher power use and more blower wear over years. Not a breakdown risk this season.
Indoor humidity is right at the dry-home lineWatch
Reading
58% at 76°, a dew point of about 60°F. EPA says keep it under 60%, ideally 30–50%. ASHRAE uses a 60°F dew point as the line for keeping a home dry.
Means
Your system only removes water from the air while it runs. Today it ran about 9 minutes a cycle, which is short for Florida. Humidity above the line over time means persistent dampness, sticky rooms and a musty smell.
If left alone
Comfort and dampness, not a safety issue. Worth watching through the wet season.
Checked and fine
Refrigerant chargeCooling at the coilCompressor currentFan currentVoltageTemperatureFresh airFine particlesDust and pollenDrain lineContactorWiring

Your options

One repair is recommended today. The two watch items are your call. Every price shows part and labor separately, with your Comfort Plan price beside the regular price.

Needs to be fixed · Run capacitorRecommended today
This season · Air pushing too hardPick one
Optional improvement · HumidityPick one
Selected2 items$0

Prices good for 30 days. Comfort Plan members save 10% on every repair.

Next steps

You're welcome to show this report to another contractor. Every reading and its target is listed below so anyone can check our work.

FOR YOUR RECORDS: ALL 18 READINGS ›
ReadingTodayTarget / limitApril
Subcooling (TXV)10.2°F10 ±3 (plate)9.1
Superheat11.4°Finfo on TXV12.0
Suction / liquid128 / 338 psig—124 / 331
Return air76.1° · 64.0° WB · 58%—75.8° · 62.9° WB · 55%
Supply air59.7°—58.9°
Delta T16.4°F14–18 at 64° WB16.9
Outdoor89°F—84
Total static (after filter)0.58 in≤0.50 (plate)0.66
Run capacitor41.6 µF45 ±6%43.0
Compressor amps11.8 A~12.5 expected · RLA 17.911.5
Fan amps1.1 AFLA 1.41.1
Voltage238 V208–253 (plate)241
Humidity / dew point58% / 60°F≤50 good · 60 line55% / 58°F
Temperature76.1°Fset 7675.8
CO₂740 ppm<800 good · 1,200 line810
PM2.56 µg/m³≤9 EPA good · 35 line9
PM1018 µg/m³≤50 good · 150 line22